Dissmann | Global Expert Fuse for EV | HEV | Photovoltaic | Battery | Energy Storage Solutions

Fuse Specialist Manufacturer in Shenzhen China Your Safety and Life Protect is always for our first priority

Manufacturer from China
Active Member
4 Years
Home / Products / Solar PV Fuses /

10*38 Cylindrical Solar Pv Fuses , Cartridge Fuses Electronic

Contact Now
Dissmann | Global Expert Fuse for EV | HEV | Photovoltaic | Battery | Energy Storage Solutions
City:shenzhen
Country/Region:china
Contact Person:MrCK Loh
Contact Now

10*38 Cylindrical Solar Pv Fuses , Cartridge Fuses Electronic

Ask Latest Price
Video Channel
Brand Name :Dissmann
Model Number :10*38
Certification :UL,TUV
Place of Origin :China
MOQ :100pcs
Price :Negotiable
Payment Terms :T/T, L/C
Supply Ability :1,000,000pcs
Delivery Time :5-8days
Packaging Details :Standard Carton Packing
Material :Ceramic
Colour :White
Rated Current :20A-100A
Rated Voltage :80VDC-1000VDC
Breaking Capacity :DC33KA
Keyword :Solar PV fuse
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

10*38mm 500VAC Solar PV Cartridge Fuse

1.Basic Information:

Rated Current:20A-100A

Rated Voltage:80VDC-1000VDC

Breaking Capacity:AC33KA

Meet the requirement:UL248,IEC60127,EU and ROSHS Detective

2.Applicable Standards:

2.1HD10X series products comply with the related standard UL248.

3.Product Material:

Component

Material

Quantity

Wire

Silver-copper alloy

1

Cap

Tin plated copper alloy

2

Body

Ceramic tube

1

Filler

Fuse sand

Amount

4.Technical Data:

Part Number

Current Rating(Ampers)

Energy Integrals I2T(A2S)

HD10X-1A 1 0.371
HD10X-1.5A 1.5 0.835
HD10X-2A 2 4.09
HD10X-3A 3 10
HD10X-5A 5 38.4
HD10X-6.3A 6.3 71.4

5.Product Dimension:

10*38 Cylindrical Solar Pv Fuses , Cartridge Fuses Electronic

6.Electrical Performances

6.1,Test Condition

All electrical tests are conducted at an ambient temperature of 25±3℃. The ambient temperature is not allowed to vary more than 5℃ during the test, and must be within these limits.

6.2,Current-Rating Capacity Test

When the fuse links to 100% times the rated current of the conditions tested, the circuit in 4 hour should not be disconnected, the fuse is not current melt, the tube is not broken.

6.3,Pre-Arcing Time-Current Characterisitc

When the current in the following table is passing the fuse, its opening time must be in accordance with the requirements in the following table, that is, the pre-arcing time. Moreover, neither damage of the fuse-tube nor shattering of the cap shall occur.

熔断电流/ % of Rated Current 熔断时间/ Open Time
200% <2min

7,Packing Details

7.1,Packing Quantity

10pcs per inner small box,10pcs small box per inner big box.

B:10 inner big box per.

C:Each small box with 1 small packaging label,Each box with 1 packaging label,Each box with 1 Outgoing inspection report.

Note: this package is for reference only, and the actual packing is the criterion.

7.2,Packing shall be so carried out that the products will not absorb moisture or be damaged during transportation or storage.

Inquiry Cart 0